Product Details:
Minimum Order Quantity | 1 Number |
Application | HFM-3-OVL (for over load detection) or HFM-3-OPL (for open load detection) |
Model Number | HFM-3 |
Size | 110 x 110 x 50 mm |
Brand | LIBRATHERM |
Available Configuration | Three phase single heating zone or single phase 3 independent heating zone. |
Reference Signal | To be derived from the external temperature controller in the form of 4-20mA/0-5V/DC pulse/Potential |
Current Feedback | Max. 20A for each heater through built in CT or using external CT of 5A ratio. |
Fault Output | Relay changeover contacts - 3 nos. of NO-C-NC contacts for 3 sets of heater loads, with LED indicati |
Load Type | Suitable for resistive heating load single phase x 3 or three phase x 1 |
Aux Supply Voltage | 230VAC +/-10%, 50/60Hz @ max.4A |
Mounting | DIN rail or stud mount. |
DESCRIPTION:
In the heating process, it is very important to ensure that the electrical heaters remain healthy, however over a period of time, practically heaters do have tendency to either go open due to break in the heating element or two close elements likely to get short with each other and comes in parallel thereby effective resistance drops and tend to draw current more than the normal rated current. When the heater goes open, it reduces the heating capacity and increases the burden on other healthy heating elements to achieve desired set temperature. When the heater shorts the current drawn increases and may lead to burning of contacts and connecting leads and wires and it may lead to fire hazard. To safeguard the process operation against such heater behavior, it is indispensable to monitor the status of heaters on continuous basis. The only way to detect the heater status is to monitor the current flowing through it.
HFM-3 is designed to detect the failure (open or short/over load) of any of the 3 independent or 3 phase heater load. Heater current per phase of max.20A can be allowed to pass through the individual in-built CTs (for higher load current external CT with 5A CT ratio can be used). User can pass the 3 individual load cable of max. 4 square mm through each of the 3 nos. of built-in CT. The heater failure either open or short circuiting is detected by comparing Reference input command and the maximum current through each heater under normal condition with the desired set current, adjustable using on card presets marked P1, P2 and P3. When the current through the heater exceeds the set level of current, the respective on card relay energizes and respective LED will glow. This condition will remain true till the current through the heater falls below the set level of current and then relay will de-energize and LED will go off. HFM-3 works on single phase AC supply of 230VAC+/10% @ max. 4VA. It can be mounted on 35mm C rail or G rail. While placing the order, user may specify the requirement type HFM-3-OVL (for over load detection) or HFM-3-OPL (for open load detection), based on the likelihood of heater fail condition, since, HFM-3 can detect any one condition at a time.
Additional Information: